OWNER'S AND INSTALLER'S MANUAL"Manufactured in North America"Models: 5120, 5130, & 5140Applicable to Software Version 2.00 - 2
(shipped in box above electrical compartment)Refer to Pages 3.04-3.05 MODEL ELEMENTS SHIPPING AND PACKAGING
PLACEMENT AND CLEARANCE REQUIREMENTS
BRICK LOADING Load the brick, one row at a time, using a left side, right side, center pat-tern. Start at the back of the brick core and work forward
HEATING ELEMENT AND AIR CHANNEL INSTALLATIONStep 1 After all brick are loaded, insert the heating elements between the brick layers, sliding them in
BRICK CORE TEMPERATURE SENSOR INSTALLATIONStep 1 the galvanized front panel
Installation 3.05 Comfort Plus HydronicComfort Plus Hydronic Installation 3.06SAMPLE SYSTEM IDENTIFICATION LABELFIGURE 8JUNCTION BOX INSTALLATIO
LOW VOLTAGE ELECTRICAL CONNECTIONS - PEAK CONTROL
LINE VOLTAGE PEAK CONTROLLine voltage control is also an option, but is not the preferred method of control as it is usually more complex and expensiv
P1CP9RP2APPAux.RelayPeakInputsGTH5110DRCWYHoneywellRc(If being used in the application)Air Conditioner ConnectionsCYThe W/E Jumper must be removedHydr
The W/E Jumper must be removedThe Y1/Y2 Jumper must be removedInputsPeakP7LV Circuit BoardComfort Plus To Control BoardP10Fid 2RLY1D4D6R2R1P11D3D7D5W
The equipment described herein is intended for installation by a qualied technician in compliance with applicable local, state, and national codes
PLUMBINGThe Comfort Plus Hydronic heating system MUST be plumbed with a primary loop and secondary (zone) loops.
STATIC PRESSURE(Feet Water Column)Based on 80 degree entry water temperature with a 50% glycol mix.
AUXILIARY LOAD CONTROLto provide control signals to other loads in the application. To do so, connect low
CONFIGURATION MENU
C006 Output Control CongurationTo determine the value, check the options desir
Step 4
AppendixASPECIFICATIONSAppendix A.01 Comfort Plus HydronicComfort Plus Hydronic Appendix A.02MODEL 19.2 24.8 28.8 37.2 38.4 4
PARTS DIAGRAMAppendixAAppendix A.01 Comfort Plus HydronicComfort Plus Hydronic Appendix A.02564651A210345681112971819131614153031292827262533535
PARTS LIST ** Optional voltages available. Contact dealer/distributo
DWG. REF. DESCRIPTION 5120 5130 5140 NO. ITEM NO. ITEM NO. ITEM NO.
SAFETY PRECAUTIONS1. Install all ceramic heat storage brick before ener-gizing the system. Failure to do so may result in equipment damage.2. Instal
INTERNAL SYSTEM WIRING DIAGRAMS - LINE VOLTAGE Line Voltage Wiring Diagram - Model 5120240V OR 208V SYSTEMS ONLYNOTE 1: Line Voltage Field Wiring Conn
Line Voltage Wiring Diagram - Model 5130240V OR 208V SYSTEMS ONLYUse copper or aluminum conductors rated for 75oC or higher for eld connection of th
Line Voltage Wiring Diagram - Model 5140240V OR 208V SYSTEMS ONLYUse copper or aluminum conductors rated for 75oC or higher for eld connection of th
Comfort Plus Hydronic Appendix A.08INTERNAL SYSTEM WIRING DIAGRAM - LOW VOLTAGEThe outdoor temperature sensor, room thermostat, and peak control de
Appendix A.09 Comfort Plus HydronicSystem Low Voltage Wiring Diagram - PSC Motor The "R" and "C" positions in the low voltag
Comfort Plus Hydronic Appendix A.10HELP MENU
Appendix A.11 Comfort Plus Hydronic Error Code Description
Limits and Right Side Saddle includedcan be removed if needed.42 5/16"Can be broken do
Appendix A.13 Comfort Plus HydronicGLOSSARYAir Separator ~ Device used to remove air from the water so the air does not get into the closed loop sy
OperationGeneral Operation ...
Registering your purchase is an essential step to ensure warranty coverage. A Warranty Registration card is included with the Owner's Manual. Si
Comfort Plus Hydronic Operation 1.01GENERAL OPERATION
CONTROL PANEL-
Comfort Plus Hydronic Operation 1.03Operation 1.02 Comfort Plus HydronicROOM TEMPERATURE CONTROL
STATIC HEAT RECOVERY UNITNOTE: In applications using the Steffes Air Handler, the static heat recovery unit would not be used.
COMFORT PLUS STAND